Delivery date: Europe, 5-10 days. Other countries - please check with our sales representative
The LUNA2000-241-2S1 model offers maximum storage capacity in a single compact outdoor unit. It is the "worry-free" solution for investors seeking the largest energy reserve available on the market in a pre-configured format.
Optimization via Artificial Intelligence The system uses AI algorithms to predict solar production and optimize the charging/discharging cycles of the 241.9 kWh battery. This ensures that you always have energy stored at the lowest possible cost. Structurally, the cabinet is designed to last for decades, featuring a reinforced structure to support the weight of over 3 tons of cutting-edge technology.
| Characteristics | Specifications |
|---|---|
| Model type | LUNA2000-241-2S1 |
| Rated capacity | 241.0 kWh |
| Maximum cycle efficiency | 91.3% |
| Depth of charge and discharge | 0~100% |
| Dimensions (L x l x Î) | 1150 mm × 1800 mm × 2100 mm |
| Weight | <2.8 T |
| Operating temperature range | -30 °C ~ 55 °C (>50°C Derating) |
| Storage temperature range | -35 °C ~ 60 °C |
| Operating humidity range | 0 ~ 100% (non-condensing) |
| Maximum operating altitude | 4,000 m |
| System Temperature Control Mode | Hybrid cooling |
| Balance mode | Active balance |
| SOC Calibration Mode | Automatic |
| Fire suppression mode | Pack-level oxygen barrier, Directional gas exhaust, Top explosion vent, Aerosol |
| Auxiliary power supply | 176~300 Vac, single phase, ≤5 kW |
| Standby power consumption | ≤150 W |
| Communication port | Ethernet / Optical fiber |
| Communication Protocol | Modbus TCP |
| Degree of protection | IP55 |
| EMC Protection Rating | Class B |
| Noise (rated operating conditions) | ≤65 dB(A) |
| Lightning protection | Type II (AC port) |
| Protection mode | Anti-islanding protection, residual current detection, insulation resistance detection, AC overcurrent protection, AC cable connection protection |
| Environment | RoHS6 |
| Certification Standards | UL9540A; UN38.3; IEC 62477-1; IEC 62040-1; IEC 61000-6-1/2/3/4; IEC 62619; IEC 60529; VDE-AR-E 2510-2/50; IEC 62933-5-1/2; IEC 61727; EN 50549; GB/T 34120 |
| Characteristics | Details |
|---|---|
| Cell material | LFP |
| Rated battery capacity | 314 Ah |
| Battery system configuration | 240S1P |
| Number of battery packs | 4 |
| Operating voltage range | 648~852 V |
| Rated DC current | 140 A |
| Characteristics | Details |
|---|---|
| PCS model type | PCS2000-108K-MB1 |
| Rated output power | 108 kW |
| Rated AC current | 155.9 A |
| AC voltage and frequency | 380 / 400 / 415 V (3P4W), 50 / 60 Hz |
| Adjustable power factor range | -1 ... +1 |
| AC current harmonics THDi (rated output power @on-grid) | ≤1.5 % |
| AC Voltage Harmonics THDu (Linear Load @ Off-Grid) | ≤2.0 % |
Note:
Nominal operating condition: In the on-grid scenario, the ambient temperature is 25°C and the AC output voltage is 400 Vac.
| No. | Item | Maximum Qty per ESS |
|---|---|---|
| 1 | LTMS (monitors temperature and humidity in the ESS) | 1 |
| 2 | Display module | 1 |
| 3 | Fire alarm horn/strobe light | 1 |
| 4 | Exhaust fan (optional) | 2 |
| 5 | Smoke detector | 1 |
| 6 | Heat detector | 1 |
| 7 | T/H sensor | 2 |
| 8 | Standard CO sensor / Explosion-proof CO sensor | 1 |
| 9 | Door status sensor | 1 |
| 10 | Door limit switch | 1 |
| 11 | Battery pack | [2,4] |
| 12 | Aerosol fire suppression device | 3 |
| 13 | PCS (converts DC voltage to AC and vice versa) | 1 |
| 14 | Lead-acid battery box (optional) | - |
| 15 | DCDC (optional) | 1 |
| 16 | SmartLogger Installation position | - |
| 17 | Water sensor | 2 |
| 18 | TRSD Host (optional) | 1 |
| 19 | Desiccant | 4 |
| 20 | RCM (ESS control) | 1 |
| 21 | Document holder | 1 |