Product Details

​Conventional single-phase UPS systems, available in 3 versions depending on the power
Power from 1 to 3 kVA
VFI-SS-111 on-line double conversion
RS232 communication port
LAN / SNMP connectivity
Uptime can be extended with additional battery cabinets
Compact design and low footprint
 
  • Brand: Legrand
  • Ups Topology: On‑Line Double Conversion
  • Kva: 1kVA - 3kVA
  • Ups Type: Computers and Servers
  • Weight: 31 kg
  • Description
  • Characteristics
  • Reviews (0)
Conventional single-phase UPS systems, available in 3 versions depending on the power
Power from 1 to 3 kVA
VFI-SS-111 on-line double conversion
RS232 communication port
LAN / SNMP connectivity
Uptime can be extended with additional battery cabinets
Compact design and low footprint

General characteristics
Nominal power (VA) 2000 
Active power (W) 1800 
Technology On-line double conversion VFI-SS-111
Waveform Sinusoidal
Architecture UPS with extendable backup time

Input characteristics
Input voltage 230 V
Input frequency 45-65 Hz ±2 % Autosensing
Input voltage range 210 V÷240 Vac at 100% load
Input power factor › 0,99

Output characteristics
Output voltage 230 V ± 1 %
Efficiency Up to 90 %
Output frequency (nominal) 50/60 Hz synchronised
Peak factor 3 : 1
THD of output voltage <3% with linear load
Permitted overload:
 - ONLINE mode  <105%
- 10 sec.  121÷150%
- 30 sec.  106÷120%
- instant transfer to bypass >151%

Bypass
Automatic, internal, synchronised, electromechanical (for overloads and operating problems)
Batteries
Backup time extension Sì
Battery voltage 48 Vdc 
Backup time (min) 5

Communication and management
Screen and signalling Multi-coloured LED status indicator, alarms and audible signalling
Communication ports 1 RS232 serial port, 1 slot for network interface connection (ex. CS121)
Emergency Power Off (EPO) Yes
Remote control Software can be downloaded free of charge

Mechanical characteristics
Dimensions (H x W x D) (mm) 322 x 151 x 444
Dimensions of battery cabinet (H x W x D) (mm) 322 x 151 x 444
Battery cabinet Net weight (kg) 31

Ambient conditions
Ambient operating temperature (°C) 0÷40
Relative humidity (%) 20÷80 non condensing
Noise at 1 m (dBA) ‹ 50
Certifications: Reference product standards EN 62040-1, EN 62040-2

Kva: 1kVA - 3kVA

Ups Topology: On‑Line Double Conversion

Ups Type: Computers and Servers

write a review


close

UPS Legrand Keor LP On-Line Double Conversion 2000VA 1800W 310156

The product was susccessfully added to your shopping cart!

View cart Ship order
close

The product was susccessfully added to your shopping cart!

View cart Ship order
close

Compare

You must add at least one product to compare products.